Tranchart

HomeProductsRing Main Unit RMUGas-insulated Ring Main UnitGas-insulated Ring Main Unit

Gas-insulated Ring Main Unit

Payment Type:
L/C,T/T
Min. Order:
1 Unit
Transportation:
Ocean,Land
Port:
Shanghai,Ningbo
Share:
  • Product Description
Overview
Product Attributes

BrandTRANCHART

Supply Ability & Additional Information

TransportationOcean,Land

Place of OriginCHANGZHOU

PortShanghai,Ningbo

Payment TypeL/C,T/T

Packaging & Delivery
Selling Units:
Unit

Gas-insulated Ring Main Unit

Details:

XGN58-12/24 Switchgear(SF6) is a kind of composite apparatus which seals all themain circuits switches in a metal enclosure and uses SF6 gas as arc-extinguishing and insulation medium. It is suitable for RMU and double radiation power supply in 12/24kV power supply circuit. The product is especially suitable for industrial and commercial zones or rural area, which have high-density power supply load and use cable feed network. Meanwhile, the RMU has the advantages of safe operation, no weather influence, easy installation, lttemaintenance and space saving, which is suitable to be installed in box-type substation. Each technical performance index conforms to iec62271-200:2003 and GB3906 standards.

Environmental conditions of use:

1 Ambient temperature: upper limit +40°C lower limit -15°C - daily average not greater than +35°C;

2 Ambient humidity: daily average relative humidity not more than 95% - monthly average relative humidity not more than 90%;

3 Altitude: Not more than 3000m above the sea level;

4 No apparent pollution of corrosive or combustible gas around. Seismic intensity not exceeding 8 degrees;

5 The surrounding air should be free from obvious contamination such as corrosive, flammable gases or water vapour;

Note:If there are special requirements, they should be negotiated between the user and the manufacturer.

Key features:

1 The main electrical part of the indoor high-voltage SF6 load switch is sealed in an insulating shell made of epoxy resin and cast by the APG process, which has the advantages of good insulation performance and resistance to foul environments. The insulating shell consists of two insulating covers, one above and the other below, which are filled with 0.05Mpa SF6 gas, and the other below with an explosion-proof membrane. In case of internal failure, the high pressure gas is released from the membrane without causing damage to the operator or other parts. SF6 gas has good arc extinguishing performance, small size, high protection level, compact and simple structure, flexible operation. Not affected by external environment, small contact wear, long electrical life.

2 The ring main unit adopts metal enclosed box structure, the height is 160cm or 185cm main switch and cabinet for solid home installation method. The cabinet is separated into two parts, the upper part includes busbar room, switch room, low voltage room, the lower part is cable room (out of the cabinet including fuse) do not affect each other. This not only improves safety but also facilitates installation and maintenance, and enables the overall replacement of the upper unit when necessary.

3 Manual and electric operation available.

4 The interlocking of the load switch, earth switch and lower door meets the requirements of the "Five Precautions":

5 When any phase fuse is blown, the load switch will be broken and cannot be closed again.

Electrical parameter of switchgear

No.

Item

unit

Parameter

1

Rated voltage

KV

12,24

2

Rated bus bar current

A

630,1250

3

Rated current

A

630

4

Rated frequency 1min

HZ

50/60

5

Rated short-time withstand current

KA

20/4,25/2

6

Rated peak withstand current

KA

50,63

7

Rated short-circuit making current

KA

50,63

8

Rated Current of load switchgear with fuse wire

A

100

9

Rated short-circuit breaking current

 

fuse

KA

31.5

Circuit Breaker

KA

20,25

10

1min Power

frequency withstand

voltage

(phase to phase/ phase-to-ground/chasm)

 

KV

42/48,65/79

lightning impulse

withstand voltage

(peak value)

(phase to phase/ phase-to-ground)

(phase to phase/ phase-to-ground

KV

75/85,125/145

 

Circuit resistance

Load switchgear

μΩ

130

Composite apparatus cabinet(not include fuse resistance)

μΩ

250

 

Circuit breaker cabinet SF6

μΩ

140

11

SF6 Rated Gas pressure

(20ºC gauge pressure)

Mpa

0.05

12

SF6 Gas annual Leakage rate

 

≤0.2%

13

Protection grade (gas filled enclosure)

 

IP67

Product Categories : Ring Main Unit RMU > Gas-insulated Ring Main Unit

Email to this supplier
  • *Subject:
  • *To:
    Mr. simon.tang
  • *Email:
  • *Message:
    Your message must be between 20-8000 characters
HomeProductsRing Main Unit RMUGas-insulated Ring Main UnitGas-insulated Ring Main Unit
Send Inquiry
*
*

simon.tang

Mr. simon.tang

SEND INQUIRY

Home

Product

Phone

About Us

Inquiry

We will contact you immediately

Fill in more information so that we can get in touch with you faster

Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.

Send